Skip to main content
Professional

Part L Changes Under the Future Homes Standard

Last updated: |Verified against GOV.UK
10 min read
By Guy Smith | DEA, SAP & SBEM Assessor

Part L (Conservation of Fuel and Power) of the Building Regulations sets the energy performance standards for new buildings in England. Under the Future Homes Standard, Part L is receiving its most significant update in decades, requiring at least 75% lower carbon emissions than homes built to the 2013 baseline, effectively ending gas heating in new builds and setting fabric standards that will make high-performance glazing and mechanical ventilation the norm.

FHS Fabric Performance Values

Look up the fabric U-values and air permeability requirements for new dwellings under the Future Homes Standard. Backstop values (the absolute maximum permitted) are unchanged from Part L 2021. The two compliance routes (HEM and SAP 10.3) use different notional dwelling values, calibrated to achieve the same overall FHS performance standard. HEM notional values are from the consultation response (March 2026); the final dwelling notional buildings document has not yet been published. SAP 10.3 values are from Appendix R of the SAP 10.3 specification.

Select a building element above to see its performance requirements.

The Journey: Part L 2013 → 2021 → FHS

The Future Homes Standard represents the third step in a progressive tightening of Part L standards. The table below compares notional dwelling values (the targets designs must meet), not backstop limits.

Part L 2013Part L 2021Future Homes Standard
Carbon reductionBaseline (0%)30% improvementAt least 75% improvement
HeatingGas boilers standardGas boilers permittedLow-carbon heating required
Solar PVNot requiredIn notional building (gas boiler route)Mandatory (Requirement L3)
Airtightness (notional)5 m³/(h·m²)5 m³/(h·m²)3 m³/(h·m²)
Wall U-value (notional)0.18 W/m²K0.18 W/m²K0.15 W/m²K
Floor U-value (notional)0.13 W/m²K0.13 W/m²K0.11 W/m²K
Roof U-value (notional)0.13 W/m²K0.11 W/m²K0.11 W/m²K
Window U-value (notional)1.40 W/m²K1.20 W/m²KBased on actual window sizes (triple glazing typically needed)
Compliance toolSAP 2012SAP 10.2HEM or SAP 10.3

The 2021 uplift (which came into force in June 2022) was explicitly described as an interim step towards the Future Homes Standard. It tightened fabric standards and introduced primary energy as a compliance metric, but still permitted gas boilers. The FHS goes much further.

Fabric Specifications

The FHS notional dwelling specification sets significantly improved fabric performance targets. While these are not prescriptive requirements (the whole-building approach allows trade-offs), they indicate the level of fabric performance that the government considers standard for FHS compliance.

External Walls: 0.15 W/m²K

The notional wall U-value tightens from 0.18 W/m²K (Part L 2021) to 0.15 W/m²K under the FHS. The backstop (limiting) value remains 0.26 W/m²K. In practice, this means:

  • Cavity walls: Full-fill mineral wool or PIR insulation in wider cavities (typically 150 mm+), or partial fill with enhanced insulation products
  • Timber frame: Deeper studs (typically 140 mm+) fully filled, often with additional external insulation layer
  • Masonry: Thicker insulation layers than current practice, potentially pushing overall wall thickness up

Ground Floors: 0.11 W/m²K

The notional floor U-value tightens from 0.13 W/m²K (Part L 2021) to 0.11 W/m²K under the FHS. The backstop remains 0.18 W/m²K. This typically requires 120–150 mm of PIR insulation below the slab or within a beam-and-block floor system, depending on the floor construction and perimeter-to-area ratio.

Roofs: 0.11 W/m²K

The notional roof U-value is 0.11 W/m²K, unchanged from Part L 2021. The backstop remains 0.16 W/m²K. For pitched roofs, this means mineral wool at joist level of approximately 350–400 mm, or equivalent performance from rigid board insulation in warm-roof constructions.

Windows and Doors

Under Part L 2021, the notional dwelling used a fixed window U-value of 1.20 W/m²K. The FHS replaces this with a new approach where window performance is calculated based on the actual dimensions of each opening in the design. In practice, triple glazing (typically 0.8–1.0 W/m²K whole-unit) will become the standard for most FHS homes, offering:

  • More consistent performance across different frame types and sizes
  • Greater margin for compliance without relying on narrow product selections
  • Improved acoustic performance and reduced condensation risk
  • Better solar control, helping manage Part O overheating requirements

Glazing Area Limits

The FHS notional dwelling specification includes guidance on glazing area as a proportion of total floor area (TFA). The notional building specification caps glazing at approximately 25% of TFA, with recommended distribution of approximately 55% south-facing and 15% north-facing to maximise beneficial solar gains while minimising heat loss.

These glazing limits interact with Part O overheating requirements and larger glazing areas, particularly south and west-facing, increase the risk of overheating in well-insulated homes.

Airtightness

The FHS notional dwelling assumes an airtightness of 3 m³/(h·m²) at 50 Pa, tightened from the Part L 2021 notional value of 5 m³/(h·m²). The backstop (limiting) value remains 8 m³/(h·m²). With typical new builds currently achieving 4–6 m³/(h·m²), the FHS notional target demands a step change in construction quality.

Achieving 3 m³/(h·m²) consistently requires:

  • Continuous air barriers designed and detailed from the outset, not applied retrospectively
  • Factory-finished cassette or panelised construction methods that deliver consistent airtightness
  • Careful service penetration design,minimising and sealing all penetrations through the air barrier
  • Pre-completion pressure testing to verify performance before handover

At this level of airtightness, mechanical ventilation becomes essential to maintain indoor air quality. The FHS notional dwelling specifies dMEV (decentralised mechanical extract ventilation), though many builders choose MVHR for its heat recovery benefits. The interaction between airtightness and ventilation strategy is critical to FHS compliance. See our Ventilation & Part F page for full details.

Heating Requirements

The FHS represents a fundamental shift in how new homes are heated. The carbon emission targets are set at a level that no fossil fuel heating system can achieve, making low-carbon heating a de facto requirement.

Heat Pumps as Standard

Air source heat pumps (ASHPs) will be the default heating technology for the majority of new homes. Ground source heat pumps (GSHPs) and shared ground loop systems are also acceptable and offer higher efficiencies, particularly in larger developments.

Heat pump design under HEM is more demanding than under SAP because the model calculates variable COP (Coefficient of Performance) at each half-hourly timestep based on actual source and sink temperatures, rather than using a simplified seasonal average. This means:

  • Flow temperatures matter more: lower flow temperatures (35–40°C) deliver higher COPs, favouring underfloor heating or oversized radiators
  • Product selection is critical: HEM requires specific make/model data from the Product Characteristics Database (PCDB)
  • Sizing must be accurate: undersized heat pumps running on back-up electric resistance heating will be penalised heavily in the calculation

Heat Networks

Heat networks with low-carbon sources are accepted as an alternative to individual heat pumps. This is particularly relevant for higher-density developments and apartment buildings where individual ASHPs are impractical. The heat network must demonstrate that the heat source meets the required carbon intensity.

Systems That Will Not Comply

The following heating systems cannot meet FHS carbon targets:

  • Gas boilers (including condensing models)
  • Oil boilers
  • Hybrid boilers (gas boiler + heat pump combination)
  • Hydrogen-ready boilers (no hydrogen grid exists and none is planned for domestic heating)
  • Direct electric heating (resistive heaters, storage heaters: with a COP of 1.0, overall dwelling performance cannot compete with heat pumps at COP 2.5+, so TER and TPER targets are not achievable)

Hot Water Changes

HEM models hot water demand very differently from SAP. Instead of a simple monthly estimate based on floor area, HEM uses individual tapping events (each shower, bath, and tap use) throughout the day, with stratified cylinder modelling that tracks temperature layers within the hot water storage tank.

This means the FHS assessment requires far more detailed data about the hot water system:

  • Individual tap flow rates and shower types (mixer, electric, thermostatic)
  • Pipework lengths and insulation between the cylinder and each outlet
  • Cylinder specifications including volume, insulation thickness, and heat loss characteristics
  • Heat pump connection details for hot water production

The practical consequence is that homes with hot water cylinders (essential for heat pump systems) are modelled more accurately, and well-designed systems with short, insulated pipe runs are properly rewarded.

Solar PV Requirements

In June 2025, the government confirmed that solar panels will become a functional requirement of the Building Regulations under the FHS. The key requirements:

  • PV coverage equivalent to 40% of the dwelling's ground floor area where feasible (AD L1 para 5.73)
  • A “reasonable amount” where shade, orientation, or roof geometry constraints apply
  • Solar-ready infrastructure (conduit, mounting points) where panels cannot be immediately installed

HEM's half-hourly modelling is particularly well-suited to assessing solar PV. Unlike SAP's annual yield estimate, HEM models generation and self-consumption at each timestep, properly rewarding:

  • Optimal panel orientation and tilt
  • Battery storage that shifts generation to evening demand
  • Heat pump scheduling to use daytime solar generation
  • Reduced grid import, reflected in both carbon and cost calculations

Thermal Bridging

Under HEM, thermal bridges are calculated at every half-hourly timestep rather than as a static annual addition. This means thermal bridging has a larger impact on the overall calculation, particularly in colder weather when heat loss through junctions is greatest.

Thermal bridge-free design, using proprietary junction details or continuous external insulation systems, becomes increasingly valuable under FHS. The alternative is to model each junction individually using thermal modelling software (to BS EN ISO 10211), which adds significant assessment cost.

Part O Interaction: Overheating

The FHS creates a tension between minimising heat loss (Part L) and preventing overheating (Part O). Highly insulated, airtight homes with large south-facing windows can overheat in summer, and HEM's half-hourly simulation captures this dynamic in detail.

Architects must balance:

  • Glazing strategy: south-facing glazing provides beneficial winter solar gains but increases summer overheating risk
  • Shading: external shading (brise-soleil, deep reveals, overhangs) is highly effective; internal blinds are less so
  • Ventilation: purge ventilation (opening windows) is the primary summer cooling strategy, but may conflict with noise requirements in urban areas
  • Thermal mass: HEM's dynamic modelling properly credits thermal mass for absorbing daytime heat and releasing it at night

Compliance Methodology

Part L compliance under the FHS is demonstrated by comparing the proposed dwelling against a notional building of the same size and shape. Each compliance route uses its own notional building specification with different fabric values (see the notional building comparison table), but both are calibrated to achieve the same overall performance standard.

Two compliance routes are available during the transition:

  • HEM: FHS assessment via the ECaaS platform, the primary route, using half-hourly simulation for the most accurate results
  • SAP 10.3, an updated version of SAP retained as an interim alternative during the dual methodology period

For full details on both routes and how to choose between them, see our Compliance Pathways page.

Frequently Asked Questions

What U-values does the Future Homes Standard require?

The FHS notional dwelling specifies U-values of 0.15 W/m²K for external walls, 0.11 W/m²K for floors, 0.11 W/m²K for roofs, 1.2 W/m²K for windows, and 1.0 W/m²K for doors. These are not absolute minimums. The whole-building performance approach allows trade-offs between elements and systems.

Does the FHS require triple glazing?

Not explicitly, but the window U-value target of 1.2 W/m²K makes triple glazing the practical standard for most new homes. While some high-performance double-glazed units can achieve this, triple glazing offers more consistent performance across different frame types and provides greater margin for compliance.

What is the airtightness requirement?

The notional dwelling targets 3 m³/(h·m²) at 50 Pa, far tighter than the current maximum of 8 m³/(h·m²). At this level, mechanical ventilation becomes essential. The FHS notional dwelling specifies dMEV (decentralised mechanical extract ventilation), though many builders choose MVHR for its heat recovery benefits.

Are gas boilers allowed under the new Part L?

No. The FHS carbon targets are set at a level that gas boilers (and all other fossil fuel heating) cannot meet. New homes will need heat pumps or connection to low-carbon heat networks. Existing homes are not affected.

What is the notional dwelling?

The notional dwelling is a reference building of the same size and shape as the proposed home. Each compliance route has its own notional specification: HEM uses the dwelling notional buildings document (walls 0.15, floors 0.11), while SAP 10.3 uses Appendix R (walls 0.18, floors 0.13). Both are calibrated to the same FHS performance standard.

How does this differ from Part L 2021?

The FHS requires at least a 75% carbon reduction (vs 30% under 2021), mandates low-carbon heating, requires solar PV, tightens airtightness targets, and significantly improves notional wall U-values (to 0.15 under HEM or 0.18 under SAP 10.3). Uses HEM or SAP 10.3 instead of SAP 10.2. See the comparison table above.

This topic is evolving

Get notified when HEM guidance changes: regulation updates, compliance deadlines, and industry analysis from a practising assessor.

No spam. Unsubscribe at any time.