Skip to main content
Technical

HEM Ventilation & Infiltration Model: HEM-TP-06 Technical Reference

Last updated: |Verified against GOV.UK
12 min read
By Guy Smith | DEA, SAP & SBEM Assessor

The Home Energy Model (HEM) models ventilation and infiltration using a pressure-driven methodology defined in technical paper HEM-TP-06, based on BS EN 16798-7:2017. At each half-hourly timestep, HEM calculates the pressure difference across every opening in the building envelope, accounting for wind speed, wind direction, indoor–outdoor temperature differences (stack effect), and mechanical system operation, then derives the resulting air flow rate through each opening using power-law relationships. This replaces SAP's simplified shelter factor approach with a physics-based simulation that captures the dynamic, time-varying nature of air movement through buildings.

Scope and Standards Basis

HEM-TP-06 covers the calculation of all air movement into, out of, and through the dwelling. This encompasses two distinct categories of air movement:

  • Purpose-provided ventilation: controlled air paths designed into the building, including mechanical supply and extract systems (MVHR, MEV), trickle ventilators, and openable windows
  • Infiltration: uncontrolled air leakage through gaps, cracks, and imperfections in the building envelope, quantified by the air permeability measured during a pressurisation test

The underlying calculation methodology is drawn from BS EN 16798-7:2017 (Energy performance of buildings: Ventilation for buildings. Part 7: Calculation methods for the determination of air flow rates in buildings including infiltration). This European standard defines a zonal air flow model that calculates pressure-driven air movement through a network of openings. HEM implements this standard within the broader dynamic simulation framework of BS EN ISO 52016-1:2017, coupling the ventilation heat loss calculation to the heat balance at each timestep.

For an accessible overview of how ventilation interacts with the Future Homes Standard, see our Ventilation & Part F guide. For architects and designers, see the architect guidance on airtightness strategy.

Air Paths: Purpose-Provided Ventilation vs Infiltration

HEM distinguishes rigorously between air paths that are intentionally designed into the building and those that result from imperfections in the building envelope. This distinction is fundamental to the pressure-driven model because each type of air path has different flow characteristics and responds differently to pressure differences.

Purpose-Provided Ventilation Paths

Purpose-provided ventilation paths include all openings that are deliberately incorporated into the building design to provide ventilation. In HEM, each purpose-provided opening is defined by:

  • Equivalent area (Aeq): the effective free area of the opening when in its ventilation position, expressed in m². Mechanical systems are specified instead by their design air flow rate, which HEM multiplies by control and system factors (1.1 overall for dwellings) and by a pressure derating factor that varies with the pressure difference across the path
  • Facade orientation: the compass direction the opening faces, which determines the wind pressure coefficient applied to it
  • Height above ground: the vertical position of the opening, which affects the stack pressure acting across it
  • Opening position: vents take a position between zero (fully closed) and one (fully open), which scales their equivalent area. HEM assumes every vent is adjustable and fully closeable, and can solve iteratively for the position that meets an optional minimum or maximum target air change rate. Windows take an opening ratio on the same basis, driven by the window-opening setpoint
  • Flow exponent (n): the exponent in the power-law flow equation, running from 0.5 (fully turbulent flow) to 1.0 (fully laminar flow). HEM uses the BS EN 16798-7:2017 default of 0.5 for windows and vents, and 0.677 for envelope leakage

The volume flow rate through a purpose-provided opening is calculated using the power-law relationship:

Q = C × (ΔP)n

Where Q is the volume flow rate (m³/s), C is the flow coefficient derived from the equivalent area and reference conditions, ΔP is the pressure difference across the opening (Pa), and n is the flow exponent.

Infiltration Paths

Infiltration represents uncontrolled air leakage through the building envelope (through gaps around windows and doors, at junctions between building elements, through service penetrations, and through the fabric itself). Unlike purpose-provided ventilation, infiltration paths cannot be individually identified or measured in situ. Instead, HEM derives the total infiltration characteristic from the air permeability test result (blower door test).

The air permeability, expressed as q50 in m³/(h·m²) at 50 Pa referenced to the total envelope area, is converted to an overall leakage coefficient for the dwelling. HEM splits that coefficient between the facades and the roof in proportion to their areas, then represents it as a small set of leakage paths at defined heights and wind angles, which respond to local pressure conditions. This approach means that infiltration on the windward side of a building can differ significantly from infiltration on the leeward side at any given timestep, a level of detail entirely absent from SAP.

The Pressure-Driven Ventilation Model

At the heart of HEM-TP-06 is the pressure-driven calculation from BS EN 16798-7. At each half-hourly timestep, the model determines the net air flow through the dwelling by calculating the pressure difference across every opening in the building envelope and solving for the resulting flow rate. The total pressure difference across any opening has three components: wind pressure, stack pressure, and mechanical system pressure.

Wind Pressure Effects

Wind creates positive pressure on the windward facades of a building and negative pressure (suction) on the leeward facades and roof. The wind pressure at any point on the building envelope is calculated as:

Pw = 0.5 × ρ × Cp × vz²

Where ρ is the air density (approximately 1.2 kg/m³), Cp is the wind pressure coefficient for the specific facade and wind direction, and vz is the wind speed at the reference height of the building, corrected for terrain roughness and local shielding.

The wind pressure coefficient (Cp) is a dimensionless value that varies with facade orientation relative to the wind direction, building geometry, and surrounding obstructions. For air flow paths less than 15 m above ground, HEM takes its Cp values from AIVC Guide 5 Tables F1 to F3, which cover one- to three-storey buildings in three shielding classes equivalent to those in BS EN 16798-7, assuming a square footprint and giving a coefficient for each wind angle in 45° increments. For a wall path below 15 m in open shielding, the coefficient is +0.7 windward (0°), −0.2 leeward (180°) and −0.5 at 90°. Above 15 m the shielding class is taken as exposed. Table B.8 of BS EN 16798-7 is used only where cross-ventilation is not possible.

Crucially, wind speed and direction vary at each timestep, drawn from the hourly weather data for the specific site location. HEM applies a terrain roughness correction to convert the meteorological wind speed (measured at 10 m height in open terrain) to the local wind speed at the building reference height, accounting for urban, suburban, or rural exposure.

Stack Pressure (Buoyancy) Effects

Stack pressure, also called the buoyancy effect, arises from the density difference between warm indoor air and cooler outdoor air. Warm air is less dense than cold air, creating a pressure distribution where the lower parts of the building experience inward pressure (outdoor air pushing in) and the upper parts experience outward pressure (indoor air pushing out). The neutral pressure level (the height at which internal and external pressures are equal) lies somewhere between the lowest and highest openings.

The stack pressure difference at height z relative to a reference height is calculated as:

ΔPs = ρo × g × (z − zref) × (Ti − Te) / Te

Where ρo is the outdoor air density, g is gravitational acceleration (9.81 m/s²), Ti and Te are the indoor and outdoor temperatures (K), and z − zref is the height difference from the reference level.

Stack effect is most significant during cold weather (when the indoor–outdoor temperature difference is greatest) and in taller buildings (where the height difference between lowest and highest openings is larger). In a typical two-storey dwelling during winter, stack-driven infiltration can contribute significantly to the total air change rate, particularly at low wind speeds when wind-driven flows are small.

Combined Pressure Calculation

At each timestep, HEM calculates the total pressure difference across every opening by combining the wind pressure, stack pressure, and any mechanical system pressure. For openings connected to a mechanical system (e.g. MVHR extract or supply terminals), the system-generated pressure is added to the natural pressure components. The net air flow through each opening is then calculated using the power-law equation, and the total ventilation rate for the dwelling is determined by summing the flows through all openings.

This combined approach means that HEM naturally captures interactions that SAP could not model:

  • Wind-assisted and wind-opposed infiltration on different facades simultaneously
  • The interplay between stack-driven flow and mechanical extract, particularly in tall buildings or at low wind speeds
  • Cross-ventilation through openings on opposite facades under specific wind conditions
  • The reduction in infiltration when a balanced MVHR system minimises the pressure difference across the envelope

MVHR Modelling in HEM

Mechanical ventilation with heat recovery is the dominant ventilation strategy for homes built to Future Homes Standard airtightness levels, and HEM models it in considerably more detail than SAP. The MVHR model in HEM accounts for three key parameters: supply and extract flow rates, heat recovery efficiency, and fan power consumption.

Heat Recovery Efficiency

The heat exchanger at the core of an MVHR unit transfers thermal energy from the warm extract air to the incoming fresh supply air. HEM models this using the declared heat recovery efficiency (ηHR) from the PCDB product data. At each timestep, the temperature of the supply air leaving the heat exchanger is calculated as:

Tsupply = Text + ηHR × (Textract − Text)

Where Text is the external air temperature, Textract is the temperature of the air being extracted from the dwelling (taken as the zone air temperature), and ηHR is the heat recovery efficiency (typically 0.85–0.95 for modern units). The heat recovered at each timestep directly reduces the space heating demand by warming the incoming ventilation air.

High-efficiency heat exchangers (those with ηHR above 0.90) are increasingly standard in FHS-targeted designs. The difference between a unit recovering 85% and one recovering 93% of heat is significant over a heating season and is properly credited in HEM's half-hourly calculation, where SAP could only apply a seasonal average.

Specific Fan Power

MVHR fans consume electrical energy to move air through the duct network. HEM models this using the specific fan power (SFP), expressed in W/(l/s), which represents the electrical power consumed per unit of air volume flow rate. The total fan energy at each timestep is:

Pfan = SFP × qv

Where qv is the total volume flow rate through the system (l/s). Fan energy is included as both an electrical demand (increasing the dwelling's electricity consumption) and as an internal heat gain (the fan motor heat is partially released into the conditioned space). Lower SFP values indicate more efficient fan and duct design.

Summer Bypass

During warm weather, recovering heat from the extract air is counter-productive: it would raise the supply air temperature above the outdoor temperature, increasing the risk of overheating. MVHR systems therefore include a summer bypass that routes the incoming air around the heat exchanger when heat recovery is not beneficial.

The MVHR model documented in HEM-TP-06 does not include a bypass control. It applies the declared heat recovery efficiency to the supply air temperature equation at every timestep, so summer bypass operation is not represented in the calculation. Designers should still specify a bypass, and the summer ventilation strategy remains central to Part O overheating assessments, which are made separately from the HEM energy calculation.

Natural Ventilation Modelling

Although MVHR will be the dominant strategy for FHS homes, HEM must also model natural ventilation for dwellings that rely on passive air movement, whether as the primary strategy (in less airtight homes that do not target FHS compliance) or as a supplementary mechanism (e.g. purge ventilation through opening windows).

Natural ventilation in HEM is modelled through purpose-provided openings such as:

  • Trickle ventilators: small, controllable openings typically located in window frames, providing continuous background ventilation. Modelled using their declared equivalent area and flow exponent
  • Openable windows: large openings that can provide high flow rates when open. HEM requires the equivalent area in the open position, the opening regime (occupant-controlled or thermostatically triggered), and the facade orientation

Passive stack ventilators are the notable exception. HEM-TP-06 excludes passive stack vents from the vent airflow paths, and passive and hybrid ducts (chimneys included) are not modelled at all: BS EN 16798-7:2017 leaves the ductwork pressure drop to be defined nationally, and without that method the standard's implicit formula cannot be solved. A solution from outside the standard is in development. Combustion appliances are likewise absent from the ventilation calculation for now, because the heat they provide is not yet modelled.

For each natural ventilation opening, HEM applies the same pressure-driven calculation as for all other air paths: the pressure difference from wind and stack effects drives air flow through the opening according to its flow characteristics. The direction of flow (inward or outward) can reverse at different timesteps depending on wind conditions and temperature differences.

This approach is particularly valuable for modelling single-sided ventilation (openings on only one facade) versus cross-ventilation (openings on opposite facades). Cross-ventilation benefits from wind-driven pressure differences across the building, while single-sided ventilation relies more heavily on stack effect and turbulent wind fluctuations, resulting in significantly lower flow rates. HEM captures this distinction naturally through the pressure-driven model, whereas SAP treated all natural ventilation in a simplified manner.

Infiltration Calculation

Infiltration (uncontrolled air leakage through the building envelope) is one of the most significant ventilation heat loss pathways, particularly in older or poorly sealed buildings. HEM's treatment of infiltration is fundamentally more sophisticated than SAP's.

Airtightness Test Data Input

The primary input for infiltration in HEM is the air permeability measured by a pressurisation (blower door) test at 50 Pa pressure difference, expressed as q50 in m³/(h·m²) referenced to the total building envelope area. Current Building Regulations set the maximum permitted air permeability at 8 m³/(h·m²) at 50 Pa. The Future Homes Standard notional dwelling assumes 4 m³/(h·m²) at 50 Pa; this represents a tight building envelope where uncontrolled infiltration is minimal and controlled mechanical ventilation is essential.

Conversion to Infiltration Paths

HEM converts the 50 Pa test result into a set of distributed infiltration paths through the following process:

  1. Convert to a leakage coefficient: The test result, its reference pressure (50 Pa or 4 Pa) and the envelope reference area are combined into an overall leakage coefficient Cleak for the dwelling, following BS EN 16798-7:2017 section B.3.3.15 with a default air flow exponent through leaks of 0.677
  2. Split between facades and roof: Cleak is divided between the facades and the roof in proportion to their surface areas (equations B.5 and B.6)
  3. Place five leakage paths: The dwelling leakage is modelled as exactly five air flow paths: four in the facades, two at 0.25 times the ventilation zone height and two at 0.75 times that height, each taking 25% of the facade coefficient, plus one roof path at full height taking all of the roof coefficient. The facade paths are placed at 45° and 135° to the wind at each timestep rather than at fixed compass orientations, and there is no floor path. Leaks are not assigned to particular elements, so external and party walls are not differentiated
  4. Calculate timestep flows: At each half-hourly timestep, the pressure difference across each leakage path is calculated from the combined wind and stack pressures, and the resulting flow rate is determined using the power-law equation

This distributed approach means that HEM correctly models directional infiltration: wind-driven infiltration on the windward facade and exfiltration on the leeward facade occurring simultaneously. SAP, by contrast, applied a single correction factor to derive an average infiltration rate for the whole building.

SAP vs HEM Ventilation Modelling

The shift from SAP to HEM represents a fundamental change in how ventilation and infiltration are modelled. The following table summarises the key differences:

AspectSAP 10.2HEM (BS EN 16798-7)
Calculation approachEmpirical monthly average using shelter factors and wind correction tablesPhysics-based pressure-driven model at each half-hourly timestep
Wind modellingRegional wind speed with simplified shelter factor (0.0–1.0 scale)Hourly wind speed and direction from site-specific weather data with terrain roughness correction and facade-specific Cp values
Stack effectNot explicitly modelled; partially captured in empirical factorsExplicitly calculated from indoor/outdoor temperature difference and opening heights at each timestep
Infiltration derivation50 Pa test result divided by 20 (fixed correction), then adjusted by shelter factorTest result converted to a leakage coefficient (BS EN 16798-7 B.3.3.15), split between facades and roof, modelled as five leakage paths
MVHR heat recoveryApplied as seasonal average efficiency to ventilation heat lossApplied at each timestep using the declared efficiency in the supply air temperature equation
MVHR fan powerIncluded as fixed annual energy consumptionCalculated at each timestep from SFP and actual volume flow rate; contributes to internal heat gains
Natural ventilationSimplified; trickle vents treated as fixed background ventilation rateEach opening modelled individually with equivalent area, orientation, height, and flow characteristics
Cross-ventilationNot distinguished from single-sided ventilationNaturally captured by pressure-driven model through facade-specific wind pressures
Time sensitivitySingle monthly value; no diurnal or weather variationHalf-hourly variation captures high-wind events, calm periods, and day/night differences
Directional infiltrationUniform infiltration rate assumed for whole buildingFive leakage paths placed relative to the wind direction at each timestep, each with its own pressure difference and flow

For a broader comparison of SAP and HEM across all calculation modules, see SAP vs HEM: What's Changed. For the regulatory context of these changes, see FHS Compliance Pathways.

Interaction with Part F Requirements

Part F (Means of Ventilation) of the Building Regulations for England sets minimum ventilation rates for dwellings to protect indoor air quality. HEM's ventilation model must be understood in the context of these regulatory requirements, because Part F defines the minimum performance standard that any ventilation system must achieve, while HEM calculates the energy consequences of that system's operation.

Part F requires:

  • Whole-dwelling ventilation rate: a minimum continuous fresh air supply set by the number of bedrooms and by floor area. Table 1.3 of AD F1 2026 runs from 19 l/s for a one-bedroom dwelling to 43 l/s for five bedrooms, adding 6 l/s per additional bedroom, and the rate must also be at least 0.3 l/s per m² of internal floor area. A dwelling with only one habitable room uses 13 l/s
  • Extract ventilation: for intermittent systems, Table 1.1 sets 30 l/s in a kitchen with a cooker hood extracting outside (60 l/s without one), 30 l/s in a utility room, 15 l/s in a bathroom and 6 l/s in sanitary accommodation. For continuous systems, Table 1.2 sets high rates of 13 l/s (kitchen), 8 l/s (utility room and bathroom) and 6 l/s (sanitary accommodation), with the continuous rate governed by the whole-dwelling rate
  • Purge ventilation: the ability to rapidly ventilate any habitable room (typically through openable windows) to clear accidental pollutant releases

In HEM, the ventilation system must be defined with flow rates that at least meet these Part F minima. The model then calculates the energy impact of operating the system at these rates, including the heat loss through ventilation air (offset by any heat recovery) and the electrical energy consumed by fans. If the declared flow rates fall below the Part F minimum, the system would not comply with Building Regulations regardless of the HEM energy calculation outcome.

Practical Implications for Assessors and Designers

The pressure-driven ventilation model in HEM has significant practical implications for energy assessors, building services engineers, and architects. Understanding these implications is essential for producing accurate assessments and optimising designs.

Increased Data Requirements

HEM requires substantially more detailed ventilation input data than SAP. For each purpose-provided ventilation opening, the assessor must specify the type, equivalent area, facade orientation, and height. For mechanical systems, the make and model from the PCDB must be specified, including heat recovery efficiency, specific fan power, and volume flow rates. Where product data is not provided, the calculation falls back on standardised default assumptions instead of the unit's real tested performance.

Design Sensitivity

Because HEM models ventilation at each timestep with site-specific weather data, design decisions that had minimal impact in SAP now have measurable consequences:

  • Airtightness improvements are properly credited: reducing air permeability from 5 to 4 m³/(h·m²) produces a quantifiable reduction in infiltration heat loss that varies with weather conditions throughout the year
  • MVHR unit selection matters more: the difference between an 85% and a 93% heat recovery efficiency translates directly to reduced heating demand at every timestep
  • Site wind exposure is properly represented: a sheltered urban site will show genuinely different infiltration characteristics from an exposed rural site, based on real terrain roughness corrections rather than SAP's crude shelter factor categories
  • Building orientation relative to prevailing winds affects the distribution of infiltration across facades and the performance of natural ventilation openings

Commissioning and As-Built Data

For as-built assessments, HEM requires measured data from the completed dwelling. The airtightness test result is mandatory, and the MVHR commissioning data (measured flow rates at each terminal) should inform the assessment inputs. Poorly commissioned systems (those delivering significantly different flow rates from design intent) will produce different energy performance results than the design-stage assessment predicted.

Advanced Topics

Ventilation and the Zone Model

HEM supports user-defined thermal zones, but the ventilation calculation is not zonal. HEM-TP-06 solves the mass balance for a single ventilation zone covering the whole dwelling, so there is one air change rate per timestep rather than a per-zone air flow, and no inter-zone transfer air is modelled. The resulting air change rate is then fed into each thermal zone's heat balance through the logic set out in step 5 of HEM-TP-01. Directional detail is retained within the whole-dwelling model: the leakage paths and vents sit at particular heights and wind angles, so windward and leeward flows are resolved separately even though the dwelling is treated as one ventilation zone.

Wind Speed and Terrain Correction

HEM applies a terrain roughness correction to the meteorological wind speed to derive the local wind speed at the building reference height. This correction accounts for the reduced wind speed in urban and suburban environments compared with open terrain. It follows the logarithmic roughness-coefficient equation in BS EN ISO 15927-1:2003 section 7.2.2, which defines a terrain factor, a roughness height and a minimum height above ground for four terrain classes:

  • Open water: lowest roughness height (0.01 m); highest wind speeds at building height and the greatest wind-driven infiltration
  • Open field: roughness height 0.05 m
  • Suburban: roughness height 0.3 m; significant reduction due to surrounding buildings and vegetation
  • Urban: roughness height 1.0 m; greatest reduction and the lowest wind-driven infiltration

This terrain correction replaces SAP's simplified shelter factor, which assigned a single numerical value (0 to 1) based on a subjective assessment of the site's exposure. The terrain roughness approach in HEM is more physically rigorous and produces results that vary with wind speed and building height; tall buildings in urban areas may still experience significant wind exposure at upper levels despite being sheltered at ground level.

Interaction with the Heating Calculation

Ventilation heat loss is one of the primary heat loss pathways in the overall heat balance calculated at each timestep. The ventilation heat loss rate (in watts) is calculated as:

Qvent = ρ × cp × qv,net × (Ti − Tsupply)

Where ρ × cp is the volumetric heat capacity of air (approximately 1,200 J/(m³·K)), qv,net is the net ventilation air flow rate (m³/s), Ti is the zone internal temperature, and Tsupply is the temperature of the incoming air (which may be pre-warmed by an MVHR heat exchanger). This ventilation heat loss feeds directly into the space heating demand calculation (HEM-TP-04), which determines the energy the heating system must supply at each timestep.

The coupling between the ventilation model and the heating model means that any change to the ventilation system (a different MVHR unit, a change in airtightness target, or a different duct configuration affecting SFP) propagates directly through to the heating demand and ultimately to the dwelling's energy consumption and carbon emissions. This tight coupling is a key advantage of HEM's integrated simulation approach over SAP's sequential calculation.

Frequently Asked Questions

What is the pressure-driven ventilation model in HEM?

HEM's pressure-driven model, based on BS EN 16798-7:2017, calculates pressure differences across every opening in the building envelope at each half-hourly timestep. It accounts for wind pressures, stack effect (buoyancy), and mechanical system operation, then derives air flow through each opening using power-law relationships. This replaces SAP's simplified shelter factor approach and captures the dynamic interaction between wind, buoyancy, mechanical ventilation, and the envelope.

How does HEM model MVHR systems?

HEM accounts for MVHR supply and extract air flows, heat recovery efficiency and specific fan power (SFP). At each timestep it calculates the supply air temperature from the declared heat recovery efficiency and the fan energy from SFP and air volume flow rate. HEM-TP-06 documents no summer bypass control, so the declared efficiency applies year-round in the model. Product-specific data from the PCDB is required; without it the calculation falls back on standardised default assumptions.

How does HEM use airtightness test results?

HEM takes the airtightness index from a pressurisation test (in m³/(h·m²)), with the test reference pressure and envelope area, and converts it to a leakage coefficient per BS EN 16798-7:2017 B.3.3.15 using a default flow exponent of 0.677. That coefficient is split between facades and roof by area and modelled as five leakage paths. At each timestep, HEM calculates the actual infiltration rate from real pressure differences caused by wind and stack effect, a fundamental departure from SAP's simple correction factor.

Can HEM model natural ventilation strategies?

Yes, within limits. HEM models natural ventilation through purpose-provided openings such as trickle ventilators, air bricks and openable windows. For each opening, the model requires the equivalent area, the opening position or control schedule, and the facade orientation and height. Air flow is calculated from pressure differences due to wind and stack effect. Passive stack ventilators are not modelled. For homes targeting 4 m³/(h·m²) under the Future Homes Standard, natural ventilation alone is in any case unlikely to suffice as the primary strategy.

What is the key difference between SAP and HEM ventilation modelling?

SAP used simplified shelter factors and wind correction tables to estimate a single monthly infiltration rate. HEM uses a physics-based pressure-driven model (BS EN 16798-7) that calculates air movement through every opening at each half-hourly timestep based on actual wind speed, direction, temperature differences, and opening characteristics. This captures dynamic, time-varying ventilation behaviour that SAP's monthly averages could not represent. See our full SAP vs HEM comparison.

This topic is evolving

Get notified when HEM guidance changes: regulation updates, compliance deadlines, and industry analysis from a practising assessor.

No spam. Unsubscribe at any time.